Previous Page  70 / 100 Next Page
Information
Show Menu
Previous Page 70 / 100 Next Page
Page Background

August

2019

HYDROCARBON

ENGINEERING

68

the foam is reactive power (kVAR). For the same glass, more

beer, less foam would be better.

4

Conventional methods of PF

improvement have been to use switched capacitor banks. In a

paper presented at the Minnesota Power Systems Conference,

T. P. Speas mentioned that capacitors represent an effective

and low-cost method for improving the PF and hence

supporting the voltage on the bus.

5

However, switching

untuned capacitors in and out of the circuit daily presents

challenges with potentially setting up resonant circuits in

parallel with the power system inductive impedance. Recent

advancements in MV drive technology provide a viable

alternative to inject reactive power to the system, thereby

improving the PF. Note that if all reactive power is eliminated

from the plant, then the apparent power is equal to the real

power, and this is known as unity PF (cosine (0) = 1); a goal that

is worth pursuing but might not be economical.

The principle of injecting or absorbing reactive power

(VAR) with an MV ASD is similar in working principle to that of

a synchronous generator. From basic circuits, electric current

travels from a high potential to a low potential. Take, for

example, a synchronous generator. The rotor field winding

excitation current is varied so that the induced stator terminal

voltage is raised or lowered with respect to the connected bus

voltage. If the terminal voltage of the synchronous generator is

higher than the connected bus voltage, reactive current starts

flowing from the generator to the bus and vice versa. Active

front end voltage source inverter (VSI) ASD uses a similar

concept. Figure 3 shows a typical electrical one-line illustration

of an ASD that is set-up to do reactive power (VAR)

compensation while motoring. The ASD converter’s DC bus

voltage (2) is raised with respect to the utility bus voltage to

push reactive power (3) into the drive isolation transformer and

the system. When current flows out to the utility by raising DC

capacitor bus volts, it is effectively reactive current. The

resulting current leads the voltage if the DC bus is higher than

the system nominal and lags if the DC bus volts is less than the

system nominal. The transducer (4) creates a feedback signal to

regulate reactive power (VAR) and PF at the hold point (5),

which is usually the bus or a point higher upstream of the ASD

where the PF correction impacts the most to the end user.

Note that diode front end converter-based drives such as

12-pulse, 18-pulse or 24-pulse, cannot push current back to the

line since they are inherently non-regenerative.

The following example can be used to understand the

practical benefits of an ASD that can inject reactive power

back into the power system. Consider a pump service that calls

for the electric motor to be rated at 1000 hp (Figure 4a). This is

a typical induction motor with a 0.88 PF and 95% efficiency.

The application also requires an ASD for reducing the motor

inrush current and flow control. As mentioned before, ASDs

are rated in terms of apparent power (kVA).

Hence, to run this motor, a 1000 kVA drive

is selected. After doing the power

calculations (Figure 4a), at rated conditions,

the motor requires 424 kVAR of reactive

power. This power is supplied from the ASD

and always takes priority. However, because

the drive is an active front end converter

and has capacitors as the DC link, the drive

can also supply excess capacity back to the

bus as reactive power. ASDs that can push

reactive power to the system are known as

regenerative drives. The amount of

regeneration is limited due to ambient

temperature and the drive power rating. In

this case, the drive can regenerate up to

80% of its apparent

rating (kVA) at 30˚C

ambient. Hence, as

shown in Figure 4a,

the ASD can supply up

to 153 kVAR, assuming

the drive is running at

rated conditions. From

practical experience,

we know that the

prime mover, such as

an electric motor, is

sized 10 – 12% more

than the driven

equipment, and the

selected ASD matches

the motor rating.

Hence, the drive is

usually oversized to

Figure 3.

Electrical illustration of MV ASD for reactive power

compensation.

3

Figure 4.

Example of using ASD for power factor compensation (a) ASD sized for motor

rating, (b) ASD upsized relative to the motor rating.